Field analysis of indoor air quality in high rise and low rise green offices with radiant slab cooling systems in Malaysia

This study attempts to assess the passive design effectiveness in terms of indoor air quality in green office buildings in the tropics. Two green office buildings that incorporated the radiant slab cooling and conventional cooling system have been selected as case studies. A detailed assessment in terms of thermal comfort parameters (temperature and relative humidity), indoor pollutants’ concentration (carbon dioxide, carbon monoxide and formaldehyde) and air movement was carried out. The results showed that the thermal comfort parameters fall within the Malaysian Standard (MS1525:2007) and ASHRAE Standard-55 2010 except for the air movement in both buildings. Based on the results obtained, future buildings using the radiant slab cooling can have a better comfort level from the lesson learned from both buildings.